This document specifies the:
— field of application:
— The dimensional, the physicochemical, the design, the hydraulic, the mechanical and the acoustic characteristics of non-controllable backflow preventer with different pressure zones, family C, type A, nominal sizes DN 6 to DN 25, nominal pressure PN 10.
It is applicable to:
— Family C, type A, class “a” for general use: devices of class “a” can be capable of working:
— at any pressure up to 1 MPa (10 bar);
— with any pressure variation up to 1 MPa (10 bar);
— at a supply temperature limit of 65 °C and 90 °C for 1 h;
— Family C, type A, class “b” for specific use: devices of class “b” shall be capable of working:
— at any downstream pressure up to 0,3 MPa (3 bar);
— with any downstream pressure variation up to 0,3 MPa (3 bar); at a supply temperature limit of 65 °C and 90 °C for 1 h;
Class “b” devices can capable of operating: at any downstream pressure up to 300 kPa (3 bar), with any downstream pressure variation up to 300 kPa (3 bar) at a supply temperature limit of 65 °C and 90 °C for 1 h. Class “b” devices with specific hydraulic and non-acoustic requirements and are intended to equip filling devices physically integrated into a single-function (heating) or dual-function (heating and domestic hot water) boiler.
It specifies also:
— test methods and requirements for verifying these characteristics;
— marking;
— presentation and the delivery.
NOTE: If the word "harmonized" (marked in green) is not found in the field with the name of the directive, it means that the European standard is not cited in the OJEU.
Regulation (eu) No 305/2011 of the European Parliament and of the Council of 9 march 2011 laying down harmonised conditions for the marketing of construction products and repealing council directive 89/106/eec