IEC 60079-7:2015 ED5

Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
4. 8. 2017.

Опште информације

60.60     26. 6. 2015.

IEC

TC 31

Međunarodni standard

29.260.20  

engleski   francuski  

Kupovina

Objavljen

Jezik na kome želite da primite dokument.

Apstrakt

IEC 60079-7:2015 specifies the requirements for the design, construction, testing and marking of electrical equipment and Ex Components with type of protection increased safety "e" intended for use in explosive gas atmospheres. Electrical equipment and Ex Components of type of protection increased safety "e" are either:
- Level of Protection "eb" (EPL "Mb" or "Gb"); or
- Level of Protection "ec" (EPL "Gc"). Level of Protection "eb" applies to equipment or Ex Components, including their connections, conductors, windings, lamps, and batteries; but not including semiconductors or electrolytic capacitors. Level of Protection "ec" applies to equipment or Ex Components, including their connections, conductors, windings, lamps, and batteries; and also including semiconductors and electrolytic capacitors. The requirements of this standard apply to both Levels of Protection unless otherwise stated. For Level of Protection "eb", this standard applies to electrical equipment where the rated voltage does not exceed 11 kV r.m.s., a.c. or d.c. For Level of Protection "ec", this standard applies to electrical equipment where the rated voltage does not exceed 15 kV r.m.s., a.c. or d.c. This standard supplements and modifies the general requirements of IEC 60079-0. Where a requirement of this standard conflicts with a requirement of IEC 60079-0, the requirement of this standard takes precedence. This fifth edition cancels and replaces the fourth edition published in 2006, and constitutes a technical revision. Refer to the Foreword of the document for a complete listing of the technical changes between edition 5.0 and previous edition of the document. Keywords: electrical equipment and Ex Components with type of protection increased safety "e" intended for use in explosive gas atmospheres. The contents of the Interpretation sheet 1 of September 2016 have been included in this copy.

Životni ciklus

PRETHODNO

POVUČEN
IEC 60079-7:2006 ED4

TRENUTNO

OBJAVLJEN
IEC 60079-7:2015 ED5
60.60 Standard objavljen
26. 6. 2015.

ISPRAVKE / IZMENE

OBJAVLJEN
IEC 60079-7:2015/AMD1:2017 ED5

REVIDIRAN OD

NAPUŠTEN
IEC 60079-7 ED6